Material-Driven Failure Mechanisms in Field-Aged Overhead Line Conductors Operating in Harsh Environments
Main Article Content
Abstract
Overhead transmission line conductors are expected to maintain mechanical integrity and predictable thermal performance over multidecade service lives. Operation under harsh environmental conditions can accelerate material degradation and reduce the reliability of power delivery. This paper presents a laboratory investigation of material-driven failure mechanisms in field-aged overhead conductors extracted from long-serving transmission lines in Saudi Arabia. Multiple conductor designs, including AAAC, ACAR, ACSR (greased), ACSR/AW, and GAP, were evaluated after exposure to coastal, coastal-urban, desert-coastal, and urban environments. The study integrates layer-by-layer visual inspection, bending tests, galvanizing retention and cladding verification, torsion and tensile testing, and surface emissivity measurements. Results show that unprotected aluminium conductors exhibit severe outer-layer embrittlement and visible corrosion products, whereas greased and aluminium-clad designs retain ductility and protective coatings.
Downloads
Article Details
Section

This work is licensed under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License.
How to Cite
References
IEEE Std 738-2012, “Standard for Calculating the Current-Temperature Relationship of Bare Overhead Conductors.”
https://ieeexplore.ieee.org/document/10382442. Works remain
significant; see the declaration
ASTM B230/B230M, “Standard Specification for Aluminum 1350-H19 Wire for Electrical Purposes.”
https://store.astm.org/b0230_b0230m-07r21.html
ASTM B398, “Standard Specification for Aluminum-Alloy 6201-T81 and 6201-T83 Wire for Electrical Purposes.”
https://store.astm.org/b0398_b0398m-22.html
ASTM B498, “Zinc-Coated (Galvanized) Steel Core Wire for Use in Overhead Electrical Conductors.”
https://store.astm.org/b0498_b0498m-08.html
ASTM B502, “Standard Specification for Aluminum-Clad Steel Core Wire for Use in Overhead Electrical Aluminum Conductors.” https://store.astm.org/b0502_b0502m-10e01.html
ANSI C119.4, “Electric Connectors—Connectors for Use Between Aluminum-to-Aluminum or Aluminum-to-Copper Bare Overhead Conductors.” https://www.scribd.com/document/696131629/ANSI-NEMA-C119-4-2004-Electric-Connectors
EPRI, “Evaluation of Conductor and Connector Samples: Test Results and Analysis,” 2025.